- Product Overview
- Power Capacity
- 1 GW
- Current Capacity
- 20,000 A
- Output Voltage, Nominal
- 48 VDC
- Input Voltage, Nominal
- 208 VAC to 480 VAC; three phase
- System Type
- Power Bay
- Input
- Input Voltage, Nominal
- 208 VAC to 480 VAC; three phase
- Input Voltage, Operational
- 408-528 VAC to 176-264 VAC
- Equipment Dimensions (H x W x D)
- Combo Bay List 1 and List 11 93.5" x 24" x 30", 830 lbs., Combo Bay List 2 and List 12 84" x 24" x 30", 830 lbs., AC Distribution Bay (PDSC): 84" x 1
- Access
- Front and rear
- Output
- Output Voltage, Nominal
- 48 VDC
- Output Voltage, Operational
- 42.0 VDC to 58.0 VDC
- Output Capacity
- 12,000 W rectifier
- Peak Efficiency
- 96.1% (480 VAC), 95.7% (208 VAC)
- Load Circuit Breakers / Fuses
- TPS/TLS, TPL Fuses or GJ/218-Style breakers
- Environmetal & Standard Compliance
- Control and Monitoring
- MAC controller with optional monitor LMS1000
- Operating Temperature
- 0 °C to +40 °C (+32 °F to +104 °F)
- Safety Compliance
- UL Listed (UL1801), CSA 22.2 (No. 225), c UL, NEBS Level 3