NetSure 512 582137000 up to 100A
The NetSure 512 Series, a compact -48/+24 volt up to 100 A DC power solution, features an advanced control unit, up to (4) positions for 2000 W high-efficiency eSure rectifiers and up to (2) positions for 1500 W -48 V to +24 V converters.
Saved This Product to Your Dashboard
You just saved this product to your dashboard to view at a later time. You can easily remove the item from your dashboard when you no longer wish to have it saved.
Please login or create an account to save this for later
- Telecom
NetSure 512 582137000 up to 100A
The NetSure 512 Series, a compact -48/+24 volt up to 100 A DC power solution, features an advanced control unit, up to (4) positions for 2000 W high-efficiency eSure rectifiers and up to (2) positions for 1500 W -48 V to +24 V converters.
- Telecom
Benefits
Features
Specifications
- Product Overview
- Power Capacity
- 2-4.8kW / 1.5kW
- Current Capacity
- 40-100A / 50A
- Output Voltage, Nominal
- -48VDC, +24VDC
- Input Voltage, Nominal
- Single phase: 208VAC to 240VAC
- System Type
- Single row system
- Input
- Input Voltage, Nominal
- Single phase: 208VAC to 240VAC
- Input Voltage, Operational
- Rectifier: (Single Phase) 85 VAC to 300 VAC, DC-DC Converter: 41 VDC to 58.5 VDC
- Input Connections
- Molex for AC cords or hardwiring
- Equipment Dimensions (H x W x D)
- Distribution cabinet: 4U x 23" x 14.25", Module shelf: 1U x 23" x 15"
- Access
- Top or rear cabled with front and top access
- Output
- Output Voltage, Nominal
- -48VDC, +24VDC
- Output Voltage, Operational
- Rectifier: -42 VDC to -58 VDC, -48V to +24V Converter: +24 VDC to +28 VDC
- Output Capacity
- Up to 100 amps at -48 VDC plus redundancy, Up to 50 amps at +24 VDC plus redundancy
- Peak Efficiency
- Rectifier: 96.2%, -48V to +24V Converter: 95%
- Load Circuit Breakers / Fuses
- 1-250 A E/M or E bullet nose breakers, 3-100 A TPS/TLS fuses, 18/100 A to 15 A GMT fuses
- Physical Characteristics
- Battery Circuit Breakers / Fuses
- 1A to 250 A E/M or E breakers, Fuses 3 A to 100 A TPL/TLS
- Options
- SM-Temp
*To see model-specific downloads, you will need to go to the model-specific product page by selecting the model name in the specifications chart above.