NetSure HVT EO2 CN1
400V DC Power is designed to ensure the highest levels of efficiency and reliability. Based on flexible architecture, 400V DC power can be implemented at a wide variety of different telecom and data centers sites. Whether your site equipment powering needs include 400V DC, 48V DC, or AC Power - or a combination of all three - 400V DC can be the backbone infrastructure of a cost effective and efficient site design.
Guadar este produto no seu dashboard
Você pode guardar este produto no seu dashboard para ve-lo depois. Você pode elimina-lo com facilidade do seu dashboard quando você já no quer ve-lo lá.
Please login or create an account to save this for later
- Data Center/ Colocation / Hosting
- Telecomunicação
NetSure HVT EO2 CN1
400V DC Power is designed to ensure the highest levels of efficiency and reliability. Based on flexible architecture, 400V DC power can be implemented at a wide variety of different telecom and data centers sites. Whether your site equipment powering needs include 400V DC, 48V DC, or AC Power - or a combination of all three - 400V DC can be the backbone infrastructure of a cost effective and efficient site design.
- Data Center/ Colocation / Hosting
- Telecomunicação
Vantagens
Recursos
Especificações
This efficient, reliable family of AC to DC power systems for critical HVDC power applications combines the proven benefits of 48V DC power – modularity, scalability, ease of integration – with the cable and installation saving benefits of higher voltage distribution.
- Product Overview
- Power Capacity
- 360 kW
- Current Capacity
- 900 A
- Output Voltage, Nominal
- 400 VDC
- Input Voltage, Nominal
- 3800 VAC to 480 VAC
- System Type
- Cabinet
- Input
- Input Voltage, Nominal
- 3800 VAC to 480 VAC
- Input Voltage, Operational
- 260-530 VAC
- Input Connections
- 2 x 3-phase 4-wire / 3-phase 5-wire (Available for 630 , 800 or 1000 A input current
- Equipment Dimensions (H x W x D)
- Battery control box
- Access
- Full front access, easy front and rear maintenance, fee cabling.
- Output
- Output Voltage, Nominal
- 400 VDC
- Output Voltage, Operational
- 378 VDC
- Output Capacity
- 360 kW / 900 A
- Peak Efficiency
- 97 %
- Load Circuit Breakers / Fuses
- Fuses or MCB
- Physical Characteristics
- Battery Circuit Breakers / Fuses
- 2 x 1250 A Fuse or 2 X 1600 A Fuse
- Peso (lbs / kgs)
- 200-300 kg
- Altura (pol/mm)
- 2000 mm
- Largura (pol/mm)
- 600 mm
- Profundidade (pol/mm)
- 800 mm