NetSure 7100 Compact 582137100101-106 (19")
19" wide Vertiv™ NetSure™ 7100 Compact systems are designed for rapid deployment in telecom access network applications requiring a reliable and high density power supply up to 500 A at -48 VDC. High operating temperature (350A system rating at +65°C) coupled with high operational efficiency has a positive impact on climate system dimensioning in outdoor enclosure applications.
Se ha guardado este producto en su dashboard
Acaba de guardar este producto en su dashboard para verlo más tarde. Cuando ya no quiera tenerlo guardado, puede eliminar fácilmente el elemento de su dashboard.
Inicie sesión o cree una cuenta para guardar esto para más tarde
- Telecomunicaciones
NetSure 7100 Compact 582137100101-106 (19")
19" wide Vertiv™ NetSure™ 7100 Compact systems are designed for rapid deployment in telecom access network applications requiring a reliable and high density power supply up to 500 A at -48 VDC. High operating temperature (350A system rating at +65°C) coupled with high operational efficiency has a positive impact on climate system dimensioning in outdoor enclosure applications.
- Telecomunicaciones
Beneficios
Características
Especificaciones
- Product Overview
- Capacidad
- 24 kW
- Capacidad de corriente
- 500 A
- Voltaje de salida, nominal
- -48 VDC
- Voltaje de entrada, nominal
- 100 to 240 VAC
- Tipo de sistema
- Rack or cabinet mount
- Input
- Voltaje de entrada, nominal
- 100 to 240 VAC
- Input Voltage, Operational
- 120/208/240 VAC, single phase (operational)
- Input Connections
- Terminal block (up to 6 AWG) for individual rectifier feed
- Access
- Front and rear for installation, Front for operation and maintenance
- Output
- Voltaje de salida, nominal
- -48 VDC
- Output Capacity
- 350 A @ +65 °C; 500 A @ +40 °C
- Load Circuit Breakers / Fuses
- (21) (6 on Load 1 bus, 6 on Load 2 bus, 9 on Priority bus)
- Physical Characteristics
- Peso (lbs / kg)
- 19.1 to 24.5 kg
- Alto (pulgadas / mm)
- 6-8U (266 to 347 mm)
- Ancho (pulgadas / mm)
- 483 mm
- Fondo (pulgadas / mm)
- 395 to 420 mm
- Environmetal & Standard Compliance
- Operating Temperature
- -40°C to +65°C (-40°F to +149°F)
- Safety Compliance
- UL 62368 Recognized
- Vertiv-Netsure-7100-Compact-500A-DS-EN-NA-DC-00114-WEB
- Vertiv™ NetSure™ NCU Controller Data Sheet
- Vertiv-eSure-Rectifier-R48-3500E3-DS-EN-GL-DC
- DAS-Solutions-BR-EN-NA-OE-00152
- PSD_Vertiv-NetSure-DC-Power-Services-Maintenance_NA-ENG_Datasheet
- PSD_Vertiv-NetSure-DC-Power-Services-Test-and-Turn-Up_NA-ENG_Datasheet
* Para ver descargas específicas de modelos, debe ir a la página de producto específica del modelo al seleccionar el nombre del modelo en el gráfico de especificaciones arriba.