CW440, 440kW
The innovative Liebert CW system lets you rapidly deploy chilled water capacity, achieve higher efficiency and use less white space. It offers the industry's widest range of capacities, featuring the industry's most advanced controls and innovations, such as optimized coil design that maximizes capacity and efficiency even at high entering water temperatures.
Se ha guardado este producto en su dashboard
Acaba de guardar este producto en su dashboard para verlo más tarde. Cuando ya no quiera tenerlo guardado, puede eliminar fácilmente el elemento de su dashboard.
Inicie sesión o cree una cuenta para guardar esto para más tarde
- Banca, finanzas y seguros
- Centro de datos/Coubicación/Hosting
- Educación
- Gobierno
- Salud
- Venta minorista y mayorista
CW440, 440kW
The innovative Liebert CW system lets you rapidly deploy chilled water capacity, achieve higher efficiency and use less white space. It offers the industry's widest range of capacities, featuring the industry's most advanced controls and innovations, such as optimized coil design that maximizes capacity and efficiency even at high entering water temperatures.
- Banca, finanzas y seguros
- Centro de datos/Coubicación/Hosting
- Educación
- Gobierno
- Salud
- Venta minorista y mayorista
Beneficios
Características
Especificaciones
The Liebert CW system combines the latest innovations in coil, valve and controls technologies for optimal protection and efficiency. Units in 340kW and 440kW capacities significantly reduce the cost of deployment and maintenance and improve energy efficiency through an optimized chilled water coil design that can utilize higher entering water temperature (EWT).
- Product Specifications
- Capacidad nominal total en kBtuh [kW]
- 1,765 [517]
- Net Sensible Capacity kBtuh [kW]
- 1,529 [448]
- Flujo de aire nominal [CFM]
- 60,000
- Total Capacity
- 1,765 [517]
- Input Voltage (V/Phase/Frequency Hz)
- 460 / 3 / 60
- Nominal Airflow
- 60,000
- Airflow Direction
- Downflow
- Heat Rejection Medium
- Chilled Water
- Capacity Modulation
- Variable Speed EC Fans
- Controls and Monitoring
- Liebert iCOM Unit Control
- Physical Characteristics
- Peso (lbs / kg)
- 7024 lbs
- Peso (lbs / kg)
- 3186 kgs
- Alto (pulgadas / mm)
- 145 in
- Alto (pulgadas / mm)
- 3683 mm
- Ancho (pulgadas / mm)
- 138 in
- Ancho (pulgadas / mm)
- 3505 mm
- Fondo (pulgadas / mm)
- 60 in
- Fondo (pulgadas / mm)
- 1524 mm
* Para ver descargas específicas de modelos, debe ir a la página de producto específica del modelo al seleccionar el nombre del modelo en el gráfico de especificaciones arriba.