Vertiv™ Liebert® EFC low-GWP - The next generation indirect evaporative free cooling unit From 100 to 450 kW
Vertiv™ Liebert® EFC with low-GWP refrigerant is the next generation, indirect evaporative free cooling unit designed to cool data center applications with the future in mind. It combines the capabilities of indirect air-to-air heat exchange and evaporative cooling principles in one single unit. Together with the new composite heat exchanger, the new inverter technology with low-GWP R454B, the multi-step evaporative system, the new DX priority control logic functionality and with the WET and DX priority dual modes, it provides even higher efficiency, guarantees compliance with major bans and regulations worldwide for years to come and proves to be as a turnkey solution for rapid deployment facilitating scalability and easy maintenance. Through this cutting-edge, patented technology, the Liebert® EFC can thus achieve pPUE levels of 1.05 allowing data center owners to reach top energy efficiency, as well as minimizing their operating costs.
Saved This Product to Your Dashboard
You just saved this product to your dashboard to view at a later time. You can easily remove the item from your dashboard when you no longer wish to have it saved.
Please login or create an account to save this for later
- Banking
- Financial and Insurance
- Broadcast and Entertainment
- Construction and Engineering
- Data Center/Colocation/Hosting
- Government
- Retail and Wholesale
- Transportation
Sustainability Spotlight
- R454B refrigerant totally compliant with F-Gas regulation (EU) 2024/573 with low Global Warming Potential (GWP) of 466 as per IPCC AR4
- Inverter driven technology
- Increased annual efficiency especially at partial load thanks to the heat exchanger patented design between 5-19%
- Higher cycle of concentration for optimized water usage and reduced waste
- Wider range of water quality: reclaimed water can be utilized to run the unit
- Decreased need for chemicals in water treatment
Vertiv™ Liebert® EFC low-GWP - The next generation indirect evaporative free cooling unit From 100 to 450 kW
Vertiv™ Liebert® EFC with low-GWP refrigerant is the next generation, indirect evaporative free cooling unit designed to cool data center applications with the future in mind. It combines the capabilities of indirect air-to-air heat exchange and evaporative cooling principles in one single unit. Together with the new composite heat exchanger, the new inverter technology with low-GWP R454B, the multi-step evaporative system, the new DX priority control logic functionality and with the WET and DX priority dual modes, it provides even higher efficiency, guarantees compliance with major bans and regulations worldwide for years to come and proves to be as a turnkey solution for rapid deployment facilitating scalability and easy maintenance. Through this cutting-edge, patented technology, the Liebert® EFC can thus achieve pPUE levels of 1.05 allowing data center owners to reach top energy efficiency, as well as minimizing their operating costs.
- Banking
- Financial and Insurance
- Broadcast and Entertainment
- Construction and Engineering
- Data Center/Colocation/Hosting
- Government
- Retail and Wholesale
- Transportation
Specifications
The Vertiv™ Liebert® EFC is equipped with the most advanced industry technology. The system includes indirect air-to-air heat exchange and evaporative cooling technology all in one footprint. The Liebert® EFC is capable of reducing air temperatures by leveraging on the evaporative cooling principle and with the polymer heat exchanger designed for data center applications, it provides higher efficiency together with and increased robustness and reliability. Through this technology, the Liebert EFC with low GWP can thus achieve pPUE levels of 1.05 ensuring top energy efficiency, no water waste as well as minimized operating costs.
Benefits
Features
Find Your Area Contact
Products Support Contacts
Change
Models | Normal Cooling Capacity (kW) | Max Dry Bulb - Only Dry Cooling (°C) | Max Wet Bulb - Only Evaporative Cooling (Water Priority) (°C) | Max Wet Bulb - Evaporative + DX Cooling (°C) | Max Dry Bulb - DX Cooling only (DX Priority) (°C) | Height | Width | Depth |
---|---|---|---|---|---|---|---|---|
EFC 251 |
225 |
15.8 |
19.8 |
30.9 |
29.1 |
4675 |
3800 |
2500 |
EFC 321 |
265 |
16.0 |
19.8 |
30.1 |
28.0 |
4675 |
3800 |
2900 |
EFC 401 |
400 |
13.4 |
19.0 |
29.1 |
25.6 |
4675 |
3800 |
3400 |
EFC 441 |
400 |
16.0 |
20.0 |
30.4 |
28.0 |
4585 |
4500 |
3400 |