NetSure 502 Full DC Power System
The NetSure 502 Series, a compact -48 volt 600 A DC power solution, features an advanced control unit, up to (17) positions for 2000 W high-efficiency eSure rectifiers, and a single or dual row distribution cabinet. [Spec #582136800]
Saved This Product to Your Dashboard
You just saved this product to your dashboard to view at a later time. You can easily remove the item from your dashboard when you no longer wish to have it saved.
Please login or create an account to save this for later
NetSure 502 Full DC Power System
The NetSure 502 Series, a compact -48 volt 600 A DC power solution, features an advanced control unit, up to (17) positions for 2000 W high-efficiency eSure rectifiers, and a single or dual row distribution cabinet. [Spec #582136800]
Benefits
Features
Specifications
- Product Overview
- Power Capacity
- 18 - 28.8 kW
- Current Capacity
- 40 - 600 A
- Output Voltage, Nominal
- -48V DC
- Input Voltage, Nominal
- Single phase: 120 VAC, 208 VAC to 240 VAC
- System Type
- System
- Input
- Input Voltage, Nominal
- Single phase: 120 VAC, 208 VAC to 240 VAC
- Input Voltage, Operational
- Rectifier: (Single Phase) 85 VAC to 300 VAC
- Input Connections
- Molex for AC cords or hardwiring
- Equipment Dimensions (H x W x D)
- Distribution cabinet: 4U x 19" x 13.19" or 8U x 23" x 13.19", Module shelf: 2U x (19" or 23") x 13.19"
- Access
- Top or rear cabled with front and top access
- Output
- Output Voltage, Nominal
- -48V DC
- Output Voltage, Operational
- Rectifier: -42 VDC to -58 VDC
- Output Capacity
- Up to 600 amps at -48 VDC plus redundancy
- Peak Efficiency
- Rectifier: 96.5%
- Load Circuit Breakers / Fuses
- 1-250 A E/M or E bullet nose breakers, 3-100 A TPS/TLS fuses, 18/100 A to 15 A GMT fuses
- Physical Characteristics
- Battery Circuit Breakers / Fuses
- 1A to 250 A E/M or E breakers, 50A to 2,00A GJ Breakers, 3A to 100A TPS/TLS fuses
- Options
- Optional Battery Trays, SM-Temp, BAU, Relay racks
- Environmetal & Standard Compliance
- Control and Monitoring
- NCU with remote access via web browsers, TCP/IP & SNMP as standard
- Operating Temperature
- -40 °C to +65 °C ( 40 °F to +149 °F)
- Safety Compliance
- UL Listed (cUL)
- EMC Compliance
- Conforms to FCC rules Part 15, Subpart B, Class B; EN55022 Class B, radiated and conducted; GR-1089 Issue 4