DA250, 250 kW
The Liebert® DSE DA250, 250 kW provides new levels of performance for colocation and cloud hosting facilities, with rapid deployment, low cost of ownership, high energy efficiency and low peak power. The system is ideal for raised or non-raised floor data centers. Its pumped refrigerant economizer uses no water and requires no outside air into the data center. A packaged condenser and refrigerant pump can be rooftop mounted, making it ideal for multi-story buildings.
Saved This Product to Your Dashboard
You just saved this product to your dashboard to view at a later time. You can easily remove the item from your dashboard when you no longer wish to have it saved.
Please login or create an account to save this for later
- Data Center/Colocation/Hosting
- Education
- Government
- Healthcare
- Retail and Wholesale
- Telecom
DA250, 250 kW
The Liebert® DSE DA250, 250 kW provides new levels of performance for colocation and cloud hosting facilities, with rapid deployment, low cost of ownership, high energy efficiency and low peak power. The system is ideal for raised or non-raised floor data centers. Its pumped refrigerant economizer uses no water and requires no outside air into the data center. A packaged condenser and refrigerant pump can be rooftop mounted, making it ideal for multi-story buildings.
- Data Center/Colocation/Hosting
- Education
- Government
- Healthcare
- Retail and Wholesale
- Telecom
Benefits
Features
Specifications
The Liebert® DSE in 250kW capacity is a free cooling economization system with backup DX compressor, which achieves the high efficiency without using water. The system can achieve an annual operational PUE under 1.2., while eliminating water usage, cost and treatment. Its large condenser surface area minimizes operating and peak power to minimize generator backup or free up additional saleable IT power. Unlike heat wheels, it has no air leakage or volumetric displacement, eliminating the need for additional fan power or make-up air capacity. As a self-contained solution, Liebert® DSE system is highly scalable for fast deployment and time to market. The Liebert® DSE 250kW is comprised of a packaged pumped refrigerant economizer and a micro-channel condenser, plus an indoor CRAC unit. The system operates in free cooling or partial free cooling mode, depending upon outdoor temperatures. When criteria for economization are met, the compressors turn off and the refrigerant pump turns on to move the refrigerant through the system to reject the heat of the data center, using only a fraction of the power of a compressor. Automated economization, controlled by the advanced Liebert® iCOM™ control, maximizes the number of free cooling hours by enabling economization whenever conditions warrant, including evening and night-time hours. It also eliminates the use of water. The Liebert® DSE system was recently approved by the State of California as a prescriptive option for economization under Title 24. Additionally, the system protects against outside air contamination and reduces system wear and tear by eliminating air dampers and louvers.
Air-cooled free-cooling system with water-free economization, a rapidly deployable configuration and advanced Liebert® iCOM™ thermal controls to optimize each unit and harmonize the operation of multiple units for temperature and airflow. Highly scalable and modular design accommodates changing IT loads and is ideal for upgrading outdated or inefficient cooling systems.
- Physical Characteristics
- Weight
- 6285 lb
- Weight
- 2850 kg
- Height
- 132 1/8 in
- Height
- 3406 mm
- Width
- 120 1/8 in
- Width
- 3051 mm
- Depth
- 83 1/2 in
- Depth
- 2122 mm
- Product Specifications
- Total Nominal Capacity kBtuh [kW]
- 853 [250]
- Net Sensible Capacity kBtuh [kW]
- 853 [250]
- Nominal Airflow [CFM]
- 36,500
- Total Capacity
- 853 [250]
- Net Sensible Capacity
- 853 [250]
- Nominal Airflow
- 36,500
- Airflow Direction
- Front or Bottom Discharge
- Heat Rejection Medium
- Refrigerant
- Controls and Monitoring
- Liebert® iCOM™ unit controls
- Key Components
- CRAC, Packaged Condenser/Refrigerant Pump
*To see model-specific downloads, you will need to go to the model-specific product page by selecting the model name in the specifications chart above.